Crowcon Gasmaster is a gas detection monitoring controller at the control center. Monitor fixed-type toxic gas detectors, connected to Crowcon’s new toxic gas, flammable gas and oxygen probes. With powerful features, the module design helps users just need to equip the required number of input modules, in accordance with the requirements of measuring the characteristic gas. Gasmaster central toxic gas monitoring equipment can be easily expanded by the addition of multiple modules of sensors, gas detectors suitable.
Overview
Crowcon’s Gasmaster Central Gas detection controller is a central device that controls the connection, monitoring, detection and display of powerful, compact, flexible toxic gas concentrations, including simple operation combined with a wide range of output input functions.
Crowcon Gasmaster Gas detection center controller provides all the information you need about gas and flammable gas probes with just a glimpse. The large screen with multiple lines shows the concentration of toxic gases being monitored from all connected toxic gas probes, while allowing the system to adjust and test the use of the keys on the front of the controller. Crowcon Gasmaster central gas monitoring controllers can act as a standalone system or communicate with any warning device and control system using a choice of outputs.
Large screen
- All concentrations of toxic gases are displayed simultaneously on the controller’s screen – allowing the state of the entire system to be checked with just a glimpse.
- Warning messages can be adjusted to show the name or location of any probe that is in a warning state.
- Lcd monitors can be set to display in multiple languages.
User-friendly use
- The system list of gas probes, status messages, system icons is intuitive and easily configurable to allow changes to become simple.
- All routine functions as well as calibration operations, calibration due alerts, which can be performed from the front of the controller, regular inspections can be carried out quickly.
- Event storage features – allow the system to record a history of errors and alerts so that it can be reviewed.
Flexible input/output features
- The device also offers analogue, relay and Modbus outputs – which can be easily connected around the work area.
- Flexible – The Gasmaster Central Gas monitoring controller can connect for simultaneous monitoring of up to 4 actual probes at the complex of any type of toxic gas sensor, including toxic gas probes, fire probes, or environmental testing equipment. The software of the central gas monitoring controller allows to reconfigu and even update up instantly.
- Two alert levels are independent of each channel – which can be reconfigured to suit the requirements of each region.
- Forbidden control and easy reconfigu reconfiguator – allows control from any one point at work.
- Suitable for probes with outputs of 4~20mA or mV, reduced system cost and maintenance.
Modular Design
- You just need to buy the required number of output modules with 1,2,3 or 4 channels and the system can expand later by adding to the modules.
CROWCON GASMASTER SPECIFICATIONS
Gasmaster 1 – 1 channel toxic gas detection monitoring center controller
- Dimensions: 288 x 278 x 110 mm (11.3 x 10.9 x 4.3 inches)
- Weight: 4.5kg (10lbs)
- Packing: The device is packed in a cast aluminum box, the front is fireproof ABS plastic.
- Protection Level: IP65
- Power supply: 100-240Vac 50-60Hz Or 20-30Vdc, 60W max
- Backup battery: 1.2Ah acquy built-in
- Operating temperature range: -10°C to +50°C (14°F to +122°F)
- Input:
- Fixed gas probe with 2 or 3 4-20mA signal wires (sink or source can be connected) or flammable gas probe with mV signal.
- Fire detector: a Loop input that supports up to 20 smoke detectors or heat detectors or manually focused connection points, or a fire detector (with 4~20mA signal or digital signal connection)
- Output:
- DPCO relay – with 250Vac 8A relay power
- With warning levels: Low Alarm / High Alarm / Fault
- The Warning Output Relay can be set for an increase or decrease in alarm. Latency can be customized with low-level alerts.
- A/V alarm drive 12Vdc or 24Vdc 650mA max. drive. Suitable for +ve or -ve switched alarms
- Sound/image warning: 12Vdc or 24Vdc output voltage signal with a maximum current of 650mA. Suitable for converting +Ve or Tick signals into warning signals (speakers, lights, horns…)
- Analog signal: 4~20mA signal (current source, maximum repeating power 700Ω) or voltage 1~5Vdc (with minimum load 50KΩ
- Serial link RS-485 Modbus RTU for monitoring and control via DCS/SCADA/PLC systems
- Digital connection: RS-485 Modbus RTU standard number connection output for monitoring and control through DCS/SCADA/PLC systems
- Gateway: Optional gateway to PC and event log update
- Event Archive: Sample recording time supports up to 300 alerts, errors, or system interference events.
- Signboard: LCD back-lit display shows gas level (in ppb, ppm, % volume or % LEL units), and scrolling alpha-numeric status indication.
LED’s for Alarm, Fault, Power and Warning. Integral 85dB sounder (at 10cm) - The backlit LCD monitor shows the gas concentration (in ppb, ppm, %volume, or %LEL units), and scrolls the status indicators. The Led lights give alarms, errors, power and warnings. Built-in sound up to 85dB intensity (at a distance of 10cm).
- Certifications: EMC: EN50270, EN60945, FCC Part 15, ICES002, ATEX: EN60079-25:2010
- Approval: Validated to IEC61508 SIL2
Gasmaster 4 Gas Display Control Monitor
- Dimensions: 288 x 278 x 110 mm (11.3 x 10.9 x 4.3 inches)
- Weight: 4.5kg (10lbs)
- Packing: The device is packed in a cast aluminum box, the front is fireproof ABS plastic.
- Protection Level: IP65
- Power supply: 100-240Vac 50-60Hz Or 20-30Vdc, 60W max
- Backup battery: 1.2Ah acquy built-in
- Operating temperature range: -10°C to +50°C (14°F to +122°F)
- Input:
- One to four probes with 2 or 3 4~20mA signal wires (sink or source) or mV output flammable gas detectors.
- One to four circuits consist of up to 20 smoke or thermal probes or centrally connected points, or one to four fire detectors.
- Output:
- Low, High level alarms for each channel add up to low, high and system error alerts. The relay can be set for alarms to increase or decrease gas concentrations. Latency can be customized on low-level alarms.
- A/V alarm drive 12Vdc or 24Vdc 650mA max. drive. Suitable for +ve or -ve switched alarms
- Sound/image warning: 12Vdc or 24Vdc output voltage signal with a maximum current of 650mA. Suitable for converting +Ve or Tick signals into warning signals (speakers, lights, horns…)
- Analog signal: 4~20mA signal (current source, maximum repeating power 700Ω) or voltage 1~5Vdc (with minimum load 50KΩ
- Serial link RS-485 Modbus RTU for monitoring and control via DCS/SCADA/PLC systems
- Digital connection: RS-485 Modbus RTU standard number connection output for monitoring and control through DCS/SCADA/PLC systems
- Gateway: Optional gateway to PC and event log update
- Event Archive: Sample recording time supports up to 300 alerts, errors, or system interference events.
- Signboard: LCD back-lit display shows gas level (in ppb, ppm, % volume or % LEL units), and scrolling alpha-numeric status indication.
LED’s for Alarm, Fault, Power and Warning. Integral 85dB sounder (at 10cm) - The backlit LCD monitor shows the gas concentration (in ppb, ppm, %volume, or %LEL units), and scrolls the status indicators. The Led lights give alarms, errors, power and warnings. Built-in sound up to 85dB intensity (at a distance of 10cm).
- Certifications: EMC: EN50270, EN60945, FCC Part 15, ICES002, ATEX: EN60079-25:2010
- Approval: Validated to IEC61508 SIL2