Crowcon IRmax is an extremely compact infrared (infrared gas probe) detector that can quickly and safely detect gases and hydrocarbon vapors. The IRmax gas detection system offers the choice of just one gas detection device, a gas status display at the site, a remote gas status display, or non-intrusive calibration through an IS calibration instrument, tool, or HART handheld communication connection.
Overview
IRmax’s reliability has been proven in hot, cold, humid, solvent, salt environments, making it ideal for offshore applications.
The special optical composition of IRmax is solved with a high-strength coating that is completely resistant to errors caused by evaporation. Just as IRmax does not include optical surface heating components so the power is significantly reduced, which requires only 1W of energy.
IRMAX FEATURES
Easy to install
- Compact size – requires less space, effort and time to install.
- Wide installation option – can be mounted on the wall, positioned in a 50mm pipe or connected to ani assist box using a choice of mounting and installation accessories.
- 4~20mA industry standard output – compatible with most control systems.
- HART and RS-485 Modbus connection options
Easy maintenance
- Non-intrusive remote calibration – IR monitors can be mounted up to 30m from IRmax’s location and gas test can be applied without direct access to the probe.
- Handheld calibration equipment – IRmax gas detection heads attached to an IS isolation module can be tested and calibration using a handheld calibration accessory
- Stay-Clir optical component avoids vapor adhesion to optical components
Low cost of ownership
- Low energy consumption – only 1W is consumed, allowing for small power supply and low backup power system.
- Automatic monitoring of optical component dimming – minimal maintenance keeps prices down
SPECIFICATIONS
IRMAX
- Size: 158 x 75 x 57mm (6.2 x 2.9 x 2.3ins)
- Weight: 1.58kg (3.5lbs)
- Protection Level: IP66
- Packing: 316 stainless steel
- Power supply: 12 – 30Vdc Power consumption < 1W
- Connection: One M20 or 1/2″ NPT cable gland entry
- Output power signal:
- 4-20mA current sink or source
- 2mA dirty optics warning (at 75% obscuration, configurable)
0mA detector fault signal (at 90% obscuration, configurable)
RS-485 Modbus (optional), HART 7 (optional)
- Operating temperature range: -40°C to +75°C (-40°F to 167°F)
- Operating humidity range: 0 to 100% RH non-condensing
- Operating pressure range: Atmospheric +/- 10%
- Repeatability: +/- 2% FSD
- Drift: +/- 2% FSD per year maximum
- Response time: T-90 <4 seconds
- Compatible: Complies with EN60079-29-1
- Functional Safety: Validation to IEC61508:2010, EN50402:2005 SIL 2
- Certify:
- Ex II 2 GD/ Exd IIC T6 Gb (Tamb -40to+50°C), / T4 (Tamb -40to+75°C)/ Ex tb IIIC T135°C/ Db (Tamb -40 to +75°C)
- EMC compliance: EN50270:2006, FCC CFR47 Part 15B, ICES-003
- Zones: Certified for use in Zone 1 & 2, and Zone 21 & 2 hazardous areas
IRMAX WITH FIXED IR DISPLAY
- Size: 230 x 75 x 57mm (9 x 2.9 x 2.3ins)
- Weight: 2kg (4.4lbs)
- Protection Level: IP66
- Packing: 316 stainless steel
- Power supply: 12 – 30Vdc Power consumption < 1W
- Connection: One M20 or 1/2″ NPT cable gland entry
- Output power signal:
- 4-20mA current sink or source
- 2mA dirty optics warning (at 75% obscuration, configurable)
0mA detector fault signal (at 90% obscuration, configurable)
RS-485 Modbus (optional), HART 7 (optional)
- Operating temperature range: -40°C to +75°C (-40°F to 167°F)
- Operating humidity range: 0 to 100% RH non-condensing
- Operating pressure range: Atmospheric +/- 10%
- Repeatability: +/- 2% FSD
- Drift: +/- 2% FSD per year maximum
- Response time: T-90 <4 seconds
- Compatible: Complies with EN60079-29-1
- Functional Safety: Validation to IEC61508:2010, EN50402:2005 SIL 2
- Certify:
- Ex II 2 G Exd ia IIC T4 Gb (Tamb -40to+75°C)
- EMC compliance: EN50270:2006, FCC CFR47 Part 15B, ICES-003
- Zones: Certified for use in Zone 1 & 2, and Zone 21 & 2 hazardous areas
IRMAX WITH IS BARRIER MODULE
- Size: 261 x 75 x 57mm (2.3 x 2.9 x 2.3ins)
- Weight: 2.4kg (5.3lbs)
- Protection Level: IP66
- Packing: 316 stainless steel
- Power supply: 12 – 30Vdc Power consumption < 1W
- Connection: One M20 or 1/2″ NPT cable gland entry
- Output power signal:
- 4-20mA current sink or source
- 2mA dirty optics warning (at 75% obscuration, configurable)
0mA detector fault signal (at 90% obscuration, configurable)
RS-485 Modbus (optional), HART 7 (optional)
- Operating temperature range: -40°C to +75°C (-40°F to 167°F)
- Operating humidity range: 0 to 100% RH non-condensing
- Operating pressure range: Atmospheric +/- 10%
- Repeatability: +/- 2% FSD
- Drift: +/- 2% FSD per year maximum
- Response time: T-90 <4 seconds
- Compatible: Complies with EN60079-29-1
- Functional Safety: Validation to IEC61508:2010, EN50402:2005 SIL 2
- Certify:
- EMC compliance: EN50270:2006, FCC CFR47 Part 15B, ICES-003
REMOTE IR DISPLAY
- Size: 60 x 54 x 48mm (2.3 x 2.1 x 1.9ins)
- Weight: 0.2kg (0.4lbs)
- Protection Level: IP66
- Packing: 316 stainless steel
- Power supply: 12 – 30Vdc Power consumption < 1W
- Connection: One M20 or 1/2″ NPT cable gland entry
- Output power signal:
- 4-20mA current sink or source
- 2mA dirty optics warning (at 75% obscuration, configurable)
0mA detector fault signal (at 90% obscuration, configurable)
RS-485 Modbus (optional), HART 7 (optional)
- Operating temperature range: -40°C to +75°C (-40°F to 167°F)
- Operating humidity range: 0 to 100% RH non-condensing
- Operating pressure range: Atmospheric +/- 10%
- Repeatability: +/- 2% FSD
- Drift: +/- 2% FSD per year maximum
- Response time: T-90 <4 seconds
- Compatible: Complies with EN60079-29-1
- Functional Safety: Validation to IEC61508:2010, EN50402:2005 SIL 2
- Certification: Ex II 2 GD
- Exd ia IIC T4 Gb (Tamb -40to+75°C)
Ex tb IIIC T135°C Db (Tamb -40 to +40°C) - EMC compliance: EN50270:2006, FCC CFR47 Part 15B, ICES-003
- Exd ia IIC T4 Gb (Tamb -40to+75°C)
IRMAX SPECIFICATIONS
IRmax | IRmax with Fixed IR display | IRmax with IS Barrier Module | Remote IR Display | |
Size | 158 x 75 x 57mm (6.2 x 2.9 x 2.3ins) | 230 x 75 x 57mm (9 x 2.9 x 2.3ins) | 261 x 75 x 57mm (2.3 x 2.9 x 2.3ins) | 60 x 54 x 48mm (2.3 x 2.1 x 1.9ins) |
Weight | 1.58kg (3.5lbs) | 2kg (4.4lbs) | 2.4kg (5.3lbs) | 0.2kg (0.4lbs) |
Ingress protection | IP66 |
Enclosure material | 316 stainless steel |
Power | 12-30 Vdc. < 1W |
Connection | One M20 or 1/2″ NPT cable gland entry |
Electrical output |
4-20mA current sink or source 2mA dirty optics warning (at 75% obscuration, configurable) 0mA detector fault signal (at 90% obscuration, configurable) RS-485 Modbus (optional), HART 7 (optional) |
Operating temperature | -40°C to +75°C (-40°F to 167°F) |
Humidity | 0 to 100% RH non-condensing |
Pressure range | Atmospheric +/- 10% |
Repeatability | +/- 2% FSD |
Zero drift | +/- 2% FSD per year maximum |
Response time | T-90 <4 seconds |
Performance | Complies with EN60079-29-1 |
Functional safety | Validation to IEC61508:2010, EN50402:2005 SIL 2 |
EMC compliance EN50270:2006, FCC CFR47 Part 15B, ICES-003
Approvals |
Ex II 2 GD Exd IIC T6 Gb (Tamb -40to+50°C), T4 (Tamb -40to+75°C) Ex tb IIIC T135°C Db (Tamb -40 to +75°C) |
Ex II 2 G Exd ia IIC T4 Gb (Tamb -40to+75°C) |
Ex II 2 GD Exd ia IIC T4 Gb (Tamb -40to+75°C) Ex tb IIIC T135°C Db (Tamb -40 to +40°C) |